Housing

Terminal G or Din Mounted.

L130mm x H115mm x D50mm.

Unpluggable terminals for ease of maintenance and installation

Standard Technical Specifications

Input Voltage as standard 24 VDC (24VAC is optional)

Power consumption 40mA standby 100 mA MAX

Sensor voltage 5V DC at 100 Hz square wave.

Alarm Relay volt free change over contacts rated at 8 amps 240 v ac.

Sensitivity adjustment. 1 turn clockwise increases sensitivity.

Control fuse 1 amp 20mm quick blow.

Self resetting when water leak dries.

Optional Extras Functions

Optional extras

(OPTIONAL)Fault Lamp is a 24 VDC output active when a Fault is present.

(OPTIONAL)Alarm Lamp is a 24 VDC output active when an alarm is present.

(OPTIONAL) External horn 5 VDC at 100mA.

(OPTIONAL)Fault Relay volt free change over contacts rated at 8 amps 240 v ac.

(OPTIONAL) External mute 24 VDC to a normally open momentary pushbutton.

Alarm can  latch on by fitting a latching relay. This clears by pressing mute.